Product Knowledge

Handheld Ultrasonic Flow Meter HNF110: Temporary Flow Measurement Solution

Sep 28, 2026 Leave a message

1. Typical Scenarios for Handheld Flow Meters

 

Handheld ultrasonic flow meters provide temporary flow data for the following tasks:

Pump performance verification

Pipeline routine inspection

Equipment commissioning

Flow distribution mapping

Routine maintenance

System fault diagnosis

Calibration cross-check for inline flow meters

Flow data sampling before permanent meter selection

Application Example

Cooling water loops often have numerous branch pipes without fixed flow instrumentation. One handheld device can complete flow tests across all branches, eliminating the cost of installing permanent meters on every line.

 

2. Standard Temporary Measurement Workflow

 

The testing procedure is concise: Select measuring point → Input pipe parameters → Mount external sensors → Verify signal quality → Record flow data

HNF110 adopts external clamp-on transducers, so pipe cutting, drilling or shutdown is unnecessary. The operation manual recommends fully flooded pipes with steady flow for reliable readings. After testing, sensors can be detached and reinstalled on other pipelines instantly.

 

3. Practical Problems Solved by Temporary Flow Testing

 

Field measurement validates real operating status that drawings and equipment datasheets cannot reflect, answering core questions:

Does the pump output match its rated flow?

What is the flow split of each pipe branch?

Has flow capacity shifted after overhaul?

Are readings from existing inline flow meters accurate?

What is the actual working flow for permanent meter sizing?

 

4. Single Device for Multiple Measuring Points

 

Core advantage of portable flow meters: mobility across valid test points.

表格

Measuring Point Flow Rate
Main cooling water pipe 52 m³/h
Branch A 21 m³/h
Branch B 18 m³/h
Branch C 11 m³/h

Test data can be contrasted against design flow values. Abnormal readings help technicians trace root causes including valve mispositioning, pump degradation, clogged filters and pipeline throttling. The unit serves both flow measurement and on-site troubleshooting.

 

5. Pre-Measurement Pipeline Information Required

 

Complete pipe parameters ensure accurate measurement:

Pipe outer diameter, material, wall thickness & internal lining

Medium type, operating temperature

Expected flow range

External insulation thickness

HNF110 Compatibility

Pipe range: 15 mm ~ 6000 mm

Applicable pipes: carbon steel, stainless steel, cast iron, PVC, copper, aluminum and lined metal pipes

Valid media: single-phase uniform liquids that transmit ultrasound (water, seawater, industrial wastewater, acid & alkali solutions, alcohol, various industrial oils)

 

6. Judgment Criteria for Valid & Reliable Readings

 

Displayed flow figures alone cannot confirm valid measurement. HNF110 displays signal strength, signal quality and transit time ratio; measurements are deemed credible only when all three indicators meet standard thresholds.

Site selection rules: prioritize fully flooded pipes with stable flow. Avoid partially filled sections, heavy vibration, heavy scaling and turbulent flow zones.

 

7. Data Logging & Post-Processing

 

Complete test records include location and working conditions for later analysis:

表格

Item Sample Record
Measuring point Cooling Water Branch A
Pipe specification DN100
Medium Cooling water
Flow rate 21 m³/h
Liquid temperature 25°C
Pump status Running
Valve state Fully open
Timestamp 10:30

HNF110 built-in data logger stores up to 16,500 groups of test data. Via the Type-C port, users export data to PCs and auto-generate Excel spreadsheets for batch comparison and formal test reports.

 

8. Handheld vs Permanent Ultrasonic Flow Meters

 

Two product types target distinct application scenarios:

表格

Handheld Flow Meter Permanent Flow Meter
Short-term spot measurement 24/7 continuous monitoring
On-site inspection & auditing Real-time process control
Fault diagnosis & commissioning Long-term fixed monitoring
Reusable for dozens of pipes Dedicated to one pipeline

Handheld units excel for frequently changing test locations; permanent meters suit fixed-point continuous monitoring. Many projects combine both: engineers sample real flow data with HNF110 first, then select properly sized permanent meters based on measured operating conditions.

 

9. HONNO HNF110 Portable Ultrasonic Flow Meter Overview

 

HNF110 is a dedicated clamp-on handheld ultrasonic flowmeter for field temporary testing:

External non-intrusive transducer mounting

Coverage: 15 mm ~ 6000 mm pipe diameter

Measurement accuracy: ±1%

Built-in rechargeable battery for cable-free field operation

Type-C data export to PC for Excel report generation

It fully meets field demands for multi-point flow testing, recording, comparison and analysis.

 

Core Summary

 

For pipelines only requiring intermittent flow detection, permanent flow meter installation is uneconomical. Handheld ultrasonic flow meters deliver flexible temporary data collection across commissioning, maintenance, troubleshooting, site inspection and system flow surveys. With proper pipe parameters and qualified measuring sections, a single HNF110 completes cross-pipe testing, data logging and computer-based post-analysis.

 

Frequently Asked Questions

 

Q1: What is the function of a handheld ultrasonic flow meter?

A1: For temporary spot flow measurement, equipment commissioning, maintenance, on-site troubleshooting and cross-verification of existing flow meters.

Q2: Can one unit test multiple pipelines?

A2: Yes, as long as pipe and liquid media fall within the instrument's compatible range.

Q3: Does pipe cutting or shutdown work required for testing?

A3: No. HNF110 uses external clamp-on sensors without pipe penetration.

Q4: Does HNF110 support data storage?

A4: Yes, internal logger supports up to 16,500 data sets.

Q5: How to export stored measurement data?

A5: Transfer data to PC via Type-C interface and export as editable Excel files.

Q6: Can HNF110 calibrate inline permanent flow meters?

A6: Yes, it serves as a reference standard to compare flow readings under identical operating conditions.