Hongnuo (shenyang) General Machinery Co., Ltd. is one of the most reliable manufacturers and suppliers of flow switch thermal dispersion type in China. Welcome to buy high quality flow switch thermal dispersion type at competitive price from our factory. We also accept customized orders.
HNF10-A vs HNF10-AC – Which one fits your application?
| HNF10-A | HNF10-AC | |
| Output types | Fixed NPN or PNP | NPN, PNP, or Relay (NO+NC selectable) |
| Max load current | 80mA (transistor output) | 400mA (transistor) / 1A (relay output) |
| Media | Water, oil | Water, oil, air |
| Setpoint adjustment | Potentiometer (field adjustable) | Potentiometer (field adjustable) |
| Electrical connection | M12 plug | M8 plug |
| Typical application | Direct PLC input | Relay model drives contactors, solenoid valves, alarm lamps |
Core specs at a glance
| Parameter | Value |
|---|---|
| Media | Water, oil, air |
| Setting range | Water: 1–150 cm/s ; Oil: 3–300 cm/s ; Air: 20–2000 cm/s |
| Setting method | Potentiometer (field adjustable) |
| Output | PNP, NPN, or Relay (NO+NC selectable) |
| Max load current | 400mA (PNP/NPN) ; 1A 48V AC/DC (Relay) |
For more parameters, please click on "Specifications".
setting guide
Setting the trip point:
- Install and power on. Wait 8 seconds for initialization (green LED on, then red).
- Open the valve and let the media flow at the minimum flow rate you want to monitor.
- Turn the potentiometer counterclockwise 2–3 turns - the LED turns red.
- Turn the potentiometer clockwise slowly until the LED turns green.
- The switch is now set. The output will trigger when flow drops below this point.
Green LED = flow above setpoint. Red LED = flow below setpoint or no flow.

Where to use

Industrial equipment
Coolant lines on machine tools, injection moulding, and laser equipment. Prevents overheat shutdown.
Water treatment
Pump dry-run protection. Triggers alarm or shut-off on flow loss.
Pharmaceutical
CIP return lines and fluid transfer confirmation. Verifies flow in sanitary piping.
Power generation
Cooling water flow detection on generator sets. Transformer oil flow monitoring.
Petrochemical
Flow/no-flow status on process lines. Pump idle protection.
Installation Tips
- Probe tip must be fully immersed in the media for accurate detection.
- Vertical installation: flow direction from bottom to top (see diagram).
- Horizontal installation: probe should avoid air pockets and sediment at the bottom.
- Tightening torque: 20–30 N·m.
- M8 connector: align the slot, hand-tighten the screw. Do not rotate the housing.
- Straight pipe section recommended: ≥5× pipe diameter upstream.
|
HNF10-AC Thermal Conductivity Flow Switch Parameters |
|
|
Specific Parameters |
Value / Description |
|
Measurement Principle |
The HNF10-AC thermal conductivity flow switch is designed based on the principle of heat exchange. The probe is equipped with an internal heating module and a heat sensing module. The heat conduction of the flow switch is closely related to the flow rate of the medium. During measurement, the heating module emits heat. If there is no medium flow in the pipeline, the amount of heat received by the heat sensing module is a fixed value. When there is medium flow, the amount of heat received by the heat sensing module will change with the flow rate of the medium. The heat sensing module converts this temperature difference signal into an electrical signal, which is then converted by the processor into a corresponding standard analog signal or contact signal output. The flow switch uses this signal to display and control the flow rate of the medium. |
|
Set Range |
1...150 cm/s (water), 3...300 cm/s (oil), 20...2000 cm/s (air) |
|
Pressure Resistance Range |
100bar |
|
Medium Temperature Range |
-20~90℃ |
|
Ambient Temperature Range |
-20~80℃ |
|
Signal Output |
PNP, NPN, Relay, selectable Normally Open + Normally Closed |
|
Signal Input |
3 wires 4~20mA current input, can be used as a data acquisition device |
|
Power |
24V±20%DC |
|
Turn On The Power |
Max 400mA (PNP or NPN type) |
|
Electrical Protection |
Inversion, short circuit, overload protection |
|
Shell Material |
304 Stainless Steel |
|
Probe Material |
304 Stainless Steel |
|
Protection Level |
IP67 |
|
Weight |
0.4kg |
|
Certificate |
CE |