Hongnuo (shenyang) General Machinery Co., Ltd. is one of the most reliable manufacturers and suppliers of digital water flow switch in China. Welcome to buy high quality digital water flow switch at competitive price from our factory. We also accept customized orders.
Core specs
| Parameter | Value |
|---|---|
| Media | Water, oil, air (and other media compatible with stainless steel) |
| Setting range | Water: 1–150 cm/s ; Oil: 3–300 cm/s ; Air: 20–2000 cm/s |
| Flow indication | 8 LEDs: 3 red (< setpoint), 1 yellow (= setpoint), 4 green (> setpoint) |
| Setting method | Induction buttons or PC software (on-site adjustable) |
| Output |
PNP / NPN / Relay selectable ; NO/NC adjustable |
How it works + LED status guide
How it works
Two temperature sensors inside the probe. One measures media temperature (reference). The other is heated. Flow carries heat away – temperature difference changes with flow velocity. The electronics convert this difference into a switch signal.
LED status guide

3 red LEDs: flow is below setpoint. Switch is not actuated.
1 yellow LED: flow is at setpoint. Switch actuates.
4 green LEDs: flow is above setpoint. More green LEDs = higher flow rate.
Setting method
Set switch point via induction buttons on the unit – no tools needed. Or connect to a PC for software-based configuration.
Application
Industrial equipment
Coolant lines on machine tools, injection moulding, laser equipment. 8 LEDs show flow trend – operator sees immediately if coolant flow is dropping before machine overheats.
Water treatment
Pump dry-run protection. Triggers alarm or shut-off on flow loss. LED trend helps operators spot flow degradation before pump damage occurs.
Pharmaceutical
CIP return lines and fluid transfer confirmation. Verifies flow in sanitary piping. No moving parts means no contamination risk.
Power generation
Cooling water flow detection on generator sets. Transformer oil flow monitoring. Visual LED trend allows quick field check without opening panels.
Petrochemical
Flow/no-flow status on process lines. Pump idle protection. Stainless steel wetted parts handle corrosive media.
|
HNF10-B Thermal Flow Switch |
|
|
Specific Parameters |
Value / Description |
|
Measurement Principle |
Using the principle of thermal diffusion, there are two temperature sensors in the probe. One acts as a reference sensor to measure the medium temperature, while the other is heated and serves as the measuring sensor. The temperature difference between these two sensors is used as the basis for measuring flow rate. When the flow rate of the medium increases, the temperature difference value decreases, and vice versa. After processing, this temperature difference value is converted into a standard electrical signal output and displayed. |
|
Nominal Diameter Range |
Thread G1/2", G1/4", others customizable |
|
Wetted Parts Material |
Stainless Steel 304/Stainless Steel 316L |
|
Connection Method |
Threaded Connection |
|
Measurement Range |
Water: 1..150cm/s (default), Oil: 3...300cm/s, Air: 20..2000cm/s |
|
Maximum Process Pressure |
100bar (optional 300bar) |
|
Medium Temperature Range |
-20...85°C (-30...120°F) |
|
Ambient Temperature Range |
-40...85°C |
|
Transmitter Housing Material |
Unrestricted |
|
Display/Operation |
No display |
|
Outputs |
NPN |
|
Power Supply |
24VDC |
|
Certificate |
CE ISO9001 |
|
Functional Safety |
Functional safety follows the IEC 61508 standard, allowing its use in safety applications as stipulated by the IEC 61511 standard. |